The LEO LPP 50-28-4/2 is a single-stage, close-coupled vertical in-line centrifugal circulation pump designed for higher-capacity water circulation, heating, cooling and industrial applications. It is part of LEO's LPP vertical in-line pump range, which is intended for HVAC hot-water circulation, boiler systems, air-conditioning cooling-water circulation, waterworks, pressure boosting, water treatment and industrial auxiliary systems.
For the exact LPP50-28-4/2, LEO's published model table specifies a 4 kW motor, 2,900 rpm, 30 m³/h nominal flow, 28 m nominal head, 43 m³/h maximum flow, 33 m maximum head, and approximately 2 m NPSH required.
A Malaysian product listing identifies the pump as a 4 kW, 415 V, 50 Hz, 2" × 2" in-line pump, with a water-temperature limit of 90°C and maximum operating pressure of 16 bar.
Product Specifications
| Specification | LEO LPP 50-28-4/2 |
|---|---|
| Brand | LEO |
| Model | LPP 50-28-4/2 |
| Product Type | Vertical In-Line Circulation Pump |
| Pump Type | Single-Stage Centrifugal |
| Design | Close-Coupled |
| Motor Power | 4 kW |
| Approx. Motor Power | 5.5 HP |
| Motor Configuration | 2-Pole |
| Rated Speed | 2,900 rpm |
| Rated Flow | 30 m³/h |
| Rated Head | 28 m |
| Maximum Flow | 43 m³/h |
| Maximum Head | 33 m |
| NPSH Required | Approx. 2 m |
| Connection Size | DN50 / 2" |
| Connection Type | Flanged |
| Electrical Supply | 3-Phase |
| Typical Voltage | 380–415 V |
| Frequency | 50 Hz |
| Maximum Liquid Temperature | 90°C |
| Maximum Operating Pressure | 16 bar |
| Motor Insulation | Class F |
| Motor Protection | IP55 |
| Pump Arrangement | Vertical In-Line |
| Pump Stages | Single Stage |
| Shaft | Stainless Steel |
| Standard Impeller | Cast Iron |
| Stainless Impeller | Available for applicable configurations |
| Main Applications | HVAC, Heating, Cooling, Water Supply, Industrial |
The model-specific hydraulic figures are from the LPP50 technical table published for the LPP series.
Model Code Explanation
The model designation LPP 50-28-4/2 can generally be interpreted as:
- LPP – LEO vertical in-line pump series
- 50 – nominal DN50 / 2-inch connection
- 28 – nominal head of approximately 28 m
- 4 – 4 kW motor
- /2 – 2-pole motor configuration
The LEO model table confirms the relationship between the model designation, motor power, rated head and hydraulic performance.
Rated Hydraulic Performance
The nominal operating point of the LPP 50-28-4/2 is:
Rated Flow: 30 m³/h
Rated Head: 28 m
Motor Power: 4 kW
Speed: 2,900 rpm
A flow of 30 m³/h is equivalent to approximately:
500 L/min
The published maximum hydraulic capacity is approximately:
Maximum Flow: 43 m³/h
Maximum Head: 33 m
These maximum values are separate points on the pump's performance curve; the pump should not be interpreted as producing 43 m³/h at 33 m head simultaneously. The actual operating point depends on system resistance.
Hydraulic Performance Summary
| Parameter | Value |
|---|---|
| Rated Flow | 30 m³/h |
| Rated Flow | ≈500 L/min |
| Rated Head | 28 m |
| Maximum Flow | 43 m³/h |
| Maximum Flow | ≈717 L/min |
| Maximum Head | 33 m |
| Motor Power | 4 kW |
| Approx. Motor Power | 5.5 HP |
| Speed | 2,900 rpm |
| NPSH Required | ≈2 m |
The independent product listing gives a practical operating range of approximately 50–710 L/min and 33–23 m head, which corresponds closely with the LEO pump's published performance curve.
4 kW Motor
The LPP 50-28-4/2 is fitted with a 4 kW three-phase motor, equivalent to approximately 5.5 HP.
The motor is a 2-pole, approximately 2,900 rpm configuration at 50 Hz. The higher motor rating allows this model to deliver substantially more head than the LPP 50-12-1.1/2 and LPP 50-21-2.2/2 models.
For Malaysia, a 415 V / 50 Hz three-phase supply is a typical configuration for this model.
The electrical installation should include suitable motor overload and short-circuit protection, an isolator and appropriate earthing.
DN50 / 2-Inch Connections
The pump uses DN50 / 2-inch suction and discharge connections.
The Malaysian product listing specifies:
Connection: 2" × 2"
Voltage: 415 V
Frequency: 50 Hz
The DN50 connection makes the pump appropriate for medium-to-large HVAC, heating and industrial circulation pipelines.
When replacing an existing pump, verify:
- Pipe diameter
- Flange dimensions
- Bolt-hole pattern
- Flange standard
- Face-to-face dimension
- Pipe alignment
- Available motor clearance
Vertical In-Line Design
The LPP 50-28-4/2 is designed for vertical in-line installation, allowing the pump to be incorporated directly into the piping system.
This configuration provides several practical benefits:
- Compact installation footprint
- Reduced floor-space requirements
- Straight-through pipeline arrangement
- Convenient HVAC plant-room installation
- Suitable for commercial mechanical rooms
- Simplified integration into circulation loops
LEO specifically classifies the LPP as a vertical in-line pump and lists HVAC, air-conditioning, water supply and industrial applications for the series.
Single-Stage Centrifugal Pump
The LPP 50-28-4/2 uses a single-stage centrifugal hydraulic design.
The impeller transfers mechanical energy from the motor into the liquid, generating the pressure and flow required for circulation.
This design is suitable for applications where a single hydraulic stage can achieve the required system head. The 4 kW motor provides the additional input power necessary for the model's 28 m nominal head.
Pump Construction
The LPP series uses a robust construction intended for commercial and industrial circulation.
The LPP50 range is available with cast-iron and stainless-steel impeller configurations, depending on the specific model/configuration. The exact LPP50-28-4/2 listing identifies a cast-iron impeller.
The shaft is specified as stainless steel, while the pump uses a mechanical shaft seal for fluid containment.
Maximum Flow – 43 m³/h
The LEO technical table gives a maximum flow of approximately 43 m³/h for the LPP50-28-4/2.
This corresponds to approximately:
717 L/min
The maximum-flow figure represents the upper hydraulic capability of the pump. The actual flow in a working installation depends on system resistance.
For example, pipe friction, valves, elbows, heat exchangers, filters and cooling coils can significantly alter the actual operating point.
Maximum Head – 33 m
The published maximum head is approximately 33 m, compared with the nominal rated head of 28 m.
A 33 m water column corresponds to approximately 3.24 bar of water pressure under standard conditions.
The maximum head is generally associated with a low-flow/shut-off region of the pump curve. It should not be used as the normal design operating point.
Liquid Temperature
The LPP 50-28-4/2 is suitable for water temperatures up to approximately 90°C.
This makes it appropriate for:
- Hot-water circulation
- Central heating
- Boiler circulation
- HVAC heating
- Cooling-water systems
- Heat-exchanger circuits
- Industrial water circulation
The Malaysian product listing specifically states a maximum water temperature of +90°C.
Maximum Operating Pressure
The LPP 50-28-4/2 has a published maximum operating pressure of approximately 16 bar.
This makes the pump suitable for many pressurized commercial and industrial circulation systems, provided that the entire system—including pipework, valves, flanges, heat exchangers and other components—is rated for the required pressure and temperature.
NPSH Requirement
The published LEO technical table gives approximately 2 m NPSH required for the LPP50-28-4/2.
Adequate suction conditions are particularly important when the pump is used with hot water.
Insufficient NPSH margin can result in cavitation, causing:
- Noise
- Vibration
- Reduced flow
- Reduced pressure
- Impeller erosion
- Mechanical-seal damage
- Reduced pump service life
Motor Protection and Insulation
The LPP series uses:
Insulation Class: F
Protection Class: IP55
The Class F insulation provides a suitable thermal insulation system for commercial pump-motor applications, while the IP55 enclosure provides protection against dust ingress and water jets.
These characteristics make the motor suitable for many mechanical-room and industrial environments.
Recommended Applications
The LEO LPP 50-28-4/2 is suitable for:
- HVAC circulation
- Central heating systems
- Hot-water circulation
- Boiler circulation
- Boiler mixing systems
- Cooling-water circulation
- Air-conditioning systems
- Chilled-water circulation
- Heat-exchanger circulation
- Waterworks filtration and transfer
- Main-pipeline pressure boosting
- Water-treatment systems
- Industrial process-water circulation
- Industrial auxiliary systems
- Washing and cleaning systems
- Fire-fighting applications where the complete system meets applicable requirements
LEO's official LPP application information specifically lists HVAC hot-water circulation, boiler mix-flow and temperature mix-flow, air-conditioning cooling-water circulation, waterworks filtration and transfer, pressure boosting, boiler feeding, cooling-water circulation, water treatment, industrial auxiliary systems and fire-fighting systems.
Suitable Fluids
The pump is primarily intended for clean water and water-like liquids.
Suitable applications include:
- Clean water
- Heating water
- Chilled water
- Cooling water
- Treated process water
- Boiler circulation water
- Compatible water-based fluids
For chemically aggressive liquids, abrasive liquids or fluids containing significant solids, the pump materials and mechanical seal must be specifically checked before use.
Electrical Specification
A typical configuration for the LPP 50-28-4/2 is:
Motor Power: 4 kW
Voltage: 415 V
Phase: 3-Phase
Frequency: 50 Hz
Motor Speed: 2,900 rpm
The Malaysian listing confirms the 4 kW / 415 V / 50 Hz configuration.
The motor should be connected using correctly sized electrical protection equipment. Phase rotation should be verified during commissioning.
Installation Considerations
For proper installation:
- Confirm the required flow and head.
- Verify the DN50 / 2-inch flange dimensions.
- Check the pump's face-to-face dimension against the existing pipework.
- Ensure the suction and discharge pipework is properly supported.
- Install the pump according to the indicated flow direction.
- Avoid excessive pipe stress on the pump casing.
- Fill the system before starting the pump.
- Remove trapped air from the system.
- Confirm adequate suction pressure.
- Verify three-phase motor rotation.
- Check motor operating current after commissioning.
- Ensure adequate ventilation around the motor.
- Prevent dry running.
- Check flange connections for leakage.
- Confirm that system pressure and temperature remain within the pump's rated limits.
Pump Selection
The LPP 50-28-4/2 should be selected according to the actual system duty point, rather than simply using its maximum flow or maximum head.
The main parameters are:
Required Flow (Q)
Required Head (H)
Fluid Temperature
System Pressure
Fluid Characteristics
Electrical Supply
The model is particularly appropriate when the required duty is around 30 m³/h at 28 m head, which corresponds to its published nominal performance.
If a system requires significantly less or more flow/head, the actual pump curve should be checked.
Comparison With Previous LPP50 Models
| Specification | LPP 50-12-1.1/2 | LPP 50-21-2.2/2 | LPP 50-28-4/2 |
|---|---|---|---|
| Motor | 1.1 kW | 2.2 kW | 4 kW |
| Approx. HP | 1.5 HP | 3 HP | 5.5 HP |
| Speed | 2,900 rpm | 2,900 rpm | 2,900 rpm |
| Rated Flow | 20 m³/h | 24 m³/h | 30 m³/h |
| Rated Head | 12 m | 21 m | 28 m |
| Maximum Flow | 26 m³/h | 35 m³/h | 43 m³/h |
| Maximum Head | 15 m | 25 m | 33 m |
| Connection | DN50 | DN50 | DN50 |
| NPSH | 2 m | 2 m | 2 m |
The LPP50 technical table confirms the progression from the 1.1 kW LPP50-12 model through the 2.2 kW LPP50-21 to the 4 kW LPP50-28 model.
The LPP 50-28-4/2 therefore provides higher flow and considerably higher head than the LPP 50-21-2.2/2, making it more appropriate for systems with greater hydraulic resistance.
Key Advantages
- 4 kW motor for demanding circulation applications.
- Approximately 5.5 HP motor rating.
- 30 m³/h nominal flow.
- 28 m nominal head.
- 43 m³/h maximum flow.
- 33 m maximum head.
- 2,900 rpm two-pole motor.
- DN50 / 2-inch flanged connections.
- Compact vertical in-line configuration.
- Single-stage centrifugal design.
- Close-coupled construction.
- Stainless-steel shaft.
- Cast-iron impeller configuration.
- Class F insulation.
- IP55 motor protection.
- 16 bar maximum operating pressure.
- 90°C maximum water temperature.
- Approximately 2 m NPSH requirement.
- Suitable for HVAC, heating, cooling and industrial water circulation.
Detailed Performance Summary
| Parameter | LEO LPP 50-28-4/2 |
|---|---|
| Motor Power | 4 kW |
| Approx. Horsepower | 5.5 HP |
| Motor Type | 2-Pole / 3-Phase |
| Rated Speed | 2,900 rpm |
| Rated Flow | 30 m³/h |
| Rated Flow | ≈500 L/min |
| Rated Head | 28 m |
| Maximum Flow | 43 m³/h |
| Maximum Flow | ≈717 L/min |
| Maximum Head | 33 m |
| NPSH Required | ≈2 m |
| Connection | DN50 / 2" |
| Connection | Flanged |
| Liquid Temperature | Max. 90°C |
| Operating Pressure | Max. 16 bar |
| Motor Insulation | Class F |
| Motor Protection | IP55 |
| Impeller | Cast Iron |
| Shaft | Stainless Steel |
| Pump Configuration | Vertical In-Line |
| Pump Stages | Single Stage |
Website Product Description
LEO LPP 50-28-4/2 Vertical In-Line Circulation Pump 4kW is a high-capacity single-stage centrifugal pump designed for demanding water circulation, HVAC, heating, cooling and industrial applications. Equipped with a 4 kW three-phase, 2-pole motor operating at approximately 2,900 rpm, the pump delivers a rated flow of 30 m³/h at 28 m head, with maximum hydraulic performance of approximately 43 m³/h flow and 33 m head.
The pump features a DN50 / 2-inch flanged in-line configuration, allowing it to be integrated directly into compatible commercial and industrial pipework. Its vertical in-line construction provides a compact installation solution for mechanical rooms, HVAC plant rooms, heating systems and industrial circulation applications.
The LPP 50-28-4/2 is designed with a stainless-steel shaft and cast-iron impeller configuration, together with a mechanical seal, Class F motor insulation and IP55 protection. The pump is suitable for water temperatures up to approximately 90°C and maximum operating pressure up to 16 bar, subject to the complete system design.
Typical applications include central heating, boiler circulation, HVAC systems, air-conditioning cooling-water circulation, chilled-water systems, heat exchangers, waterworks, pressure boosting, water treatment, industrial process-water circulation and fire-fighting systems.
SEO Product Title
LEO LPP 50-28-4/2 Vertical In-Line Circulation Pump 4kW 5.5HP 3-Phase DN50
SEO Meta Description
LEO LPP 50-28-4/2 vertical in-line circulation pump with 4kW motor, 30m³/h rated flow and 28m head. DN50 flanged pump for HVAC, heating, cooling and industrial systems.
Inquiry - LEO CIRCULATION PUMPS - LPP 50-28-4/2